Huichuan frequency converter MD520 keeps displaying - H-C - fault when powered on
2025/5/5 21:29:34

Huichuan frequency converter MD520 keeps displaying - H-C - fault solution when powered on
The reasons for the continuous display of - H-C - fault on the Huichuan frequency converter MD520 during power on may include the following:
Power on self-test failed: It may be due to the inverter failing the power on self-test, resulting in the display of - H-C -. This may be caused by issues with the input power supply, poor contact of the 8-core ribbon cable connecting the driver board and control board, or damage to internal components of the frequency converter
Fan damage or stalling: The frequency converter displays "HC" and immediately shuts down after operation, which may be caused by fan damage or stalling. In this case, it is necessary to replace the fan
The methods to solve these problems include:
Check input power supply: Ensure that the input power supply of the frequency converter is connected normally and there is no short circuit or open circuit.
Re plug and unplug the 8-core ribbon cable: Check if the 8-core ribbon cable connecting the driver board and control board is in good contact, and if necessary, re plug and unplug the ribbon cable.
Replace fan: If the problem is caused by fan damage or blockage, the fan needs to be replaced.
Seeking manufacturer service: If the above methods cannot solve the problem, it is recommended to contact the manufacturer for professional repair services
Preventive measures and suggestions:
Regular maintenance: Regularly inspect all components of the frequency converter, especially the fan and connecting wires, to ensure their normal operation.
Avoid overload: Avoid overloading during use to reduce the risk of component damage.
Professional maintenance: Regularly invite professional personnel to conduct maintenance checks to ensure the long-term stable operation of the frequency converter.
1. Fault phenomenon: 2. Solution:
Poor contact of the wiring between the driver board and the control board. Re plug and unplug the 8-core and 28 core cables
Seeking manufacturer's service for damaged components on the control board
Motor or motor wire has a short circuit to ground
Hall fault